招考网【官方站】权威信息发布平台!

综采工作面供电设计(6)

时间:2012/08/28 20:36:35来源:未知 作者:86zhaokao.cn 点击:
X=0.144555+0.01794=0.162495 7.顺槽皮带机电机处短路电流I d7 计算 MYP 335+116型电缆的电阻、电抗:L 8 =20米, 阻抗参数:R o =0.683 / km, X o =0.084 / km R g1 =0.6830.02=0.0

∑X=0.144555+0.01794=0.162495


7.顺槽皮带机电机处短路电流Id7计算
MYP  3×35+1×16型电缆的电阻、电抗:L8=20米,
阻抗参数:Ro=0.683 / km, Xo=0.084 / km
Rg1=0.683×0.02=0.01366
Xg1=0.084×0.02=0.00168
∑R=0.022038+0.07958+0.01366=0.115278
∑X=0.144555+0.01794+0.00168=0.164175


8.1#调度绞车电机处短路电流Id8计算
MYP  3×10+1×6型电缆的电阻、电抗:L7=10米,
阻抗参数:Ro=2.159 / km, Xo=0.092 / km
Rg1=2.159×0.01=0.02159
Xg1=0.092×0.01=0.00092
∑R=0.022038+0.07958+0.02159=0.123208
∑X=0.144555+0.01794+0.00092=0.163415


9.2#调度绞车开关入口处短路电流Id9计算
MYP  3×16+1×10型电缆的电阻、电抗:L7=1000米,
阻抗参数:Ro=1.369 / km, Xo=0.090 / km
Rg1=1.369×1=1.369
Xg1=0.090×1=0.090
∑R=0.022038+0.07958+1.369=1.470618
∑X=0.144555+0.01794+0.090=0.252495


10.2#调度绞车电机处短路电流Id10计算
MYP  3×10+1×6型电缆的电阻、电抗:L7=10米,
阻抗参数:Ro=2.159 / km, Xo=0.092 / km
Rg1=2.159×0.01=0.02159
Xg1=0.092×0.01=0.00092
∑R=0.022038+0.07958++1.369+0.02159=1.492208
∑X=0.144555+0.01794+0.090+0.00092=0.253415


11.3#移变二次出口端的短路电流Id11计算
(1)系统阻抗
变压器二次电压1200V,容量1000kVA,系统短路容量按50MVA计算;则系统电抗为

(2)高压电缆阻抗
10kV电缆L (责任编辑:86zhaokao.cn)