1 =0.87km 查表得,R o =0.588 / km, X o =0.078 / km 高压电缆电阻、电抗: R g =0.5880.87=0.51156 X g =0.0780.87=0.06786 (3)变压器阻抗 查表得KBSGZY-1000/10型移动变电站的v s
1=0.87km
查表得,Ro=0.588 / km, Xo=0.078 / km
高压电缆电阻、电抗:
Rg=0.588×0.87=0.51156
Xg=0.078×0.87=0.06786
(3)变压器阻抗
查表得KBSGZY-1000/10型移动变电站的vs=4.5, ΔPN.T=6100W
则变压器的电阻、电抗:
0.008784
0.0648




12.6#组合开关入口处短路电流Id12计算
MYP  3×95+1×35型电缆的电阻、电抗:L13=500米,为2趟线路并用,
阻抗参数:Ro=0.247 / km, Xo=0.075 / km
Rg1=0.247×0.5/2=0.06175
Xg1=0.075×0.5/2=0.01875
∑R=0.0161564+0.06175=0.0779064
∑X=0.094592+0.01875=0.113342


13.输送机前电机处短路电流Id13计算
MYP  3×95+1×35型电缆的电阻、电抗:L13=50米,
阻抗参数:Ro=0.247 / km, Xo=0.075 / km
Rg1=0.247×0.05=0.01235
Xg1=0.075×0.05=0.00375
∑R=0.0161564+0.06175+0.01235=0.0902564
∑X=0.094592+0.01875+0.00375=0.117092


14.输送机后电机处短路电流Id14计算
MYP  3×95+1×35型电缆的电阻、电抗:L15=240米,
阻抗参数:Ro=0.247 / km, Xo=0.075 / km
Rg1=0.247×0.24=0.05928
Xg1=0.075×0.24=0.0185
∑R=0.0161564+0.06175+0.05928=0.1371864
∑X=0.094592+0.01875+0.0185=0.131842